GarageShopCalcBuild Your Dream Garage

Sizing

240V circuit for a 5 HP motor

A 5 HP single-phase motor draws 28 A at 240V (NEC Table 430.248), so the conductor must carry 35.0 A: a 35 A breaker and 8 AWG copper on a short run, NEMA 6-50R (or 14-50R if a neutral is wanted). On 120V the same motor draws 56 A, more than a 20 A household circuit can feed.

Breaker and wire by run length

5 HP at 240V
One-way runBreakerWireVoltage dropReceptacle
25 ft35 A8 AWG0.5 percentNEMA 6-50R (or 14-50R if a neutral is wanted)
50 ft35 A8 AWG0.9 percentNEMA 6-50R (or 14-50R if a neutral is wanted)
100 ft35 A8 AWG1.8 percentNEMA 6-50R (or 14-50R if a neutral is wanted)
150 ft35 A8 AWG2.7 percentNEMA 6-50R (or 14-50R if a neutral is wanted)

Wire is upsized from the breaker minimum whenever the voltage drop would pass 3 percent, which is why the gauge steps up with distance. Gauges are copper on the 60 C column of NEC Table 310.16, which is how NM-B cable is rated. At this size most garages want a hardwired connection through a disconnect rather than a plug-in receptacle, and conduit rather than cable: ask your electrician.

What 5 HP looks like on 120V

At 120V the motor pulls 56 A. The conductor must carry 70.0 A, which means a 70 A breaker, beyond the 20 A that a standard 120V receptacle circuit allows. That is the whole case for 240V: half the current in the same wire. Many 1-1/2 and 2 HP machines ship prewired for 120V and can be rewired for 240V, so check the nameplate.

Use the 240V circuit calculator for your own run length, and the voltage drop calculator for a cord.

Shop for this size

Matched to the result above.

Prices change often; the button shows today's price on Amazon.

Get the garage shop planning checklist

One printable page: measure the bay, count the circuits, list the machines, check the floor. Plus a few short emails, then a couple a month at most.

Unsubscribe anytime. You can also just read the checklist on this site.

240V circuit by motor size: the other answers

Frequently asked questions

What size breaker for a 5 HP 240V motor?

The full-load current is 28 A, times 1.25 is 35.0 A, so the next standard breaker is 35 A. The code allows a larger breaker to ride through motor starting, but this is the conservative size.

This page is researched guidance, not professional electrical, engineering or safety advice. Circuits, loads and clearances depend on your house, your service and your town: have a licensed electrician confirm any wiring, and check local code and each manufacturer's manual before you act.