A 20 x 20 ft garage shop with average insulation, normal sun, one person and 1,500 W of tools running carries about 15,718 BTU per hour of cooling load, so shop a 18,000 BTU mini-split. Poor insulation and a west wall can push that up a size or two.

Cooling load and nearest standard size

Load and unit size, 20 x 20 ft
InsulationShadedNormal sunSunny
Poor or none17,418 BTU, 18,000 unit18,718 BTU, 24,000 unit20,668 BTU, 24,000 unit
Average14,718 BTU, 18,000 unit15,718 BTU, 18,000 unit17,218 BTU, 18,000 unit
Good13,368 BTU, 18,000 unit14,218 BTU, 18,000 unit15,493 BTU, 18,000 unit

The load is 400 sq ft x 25 BTU/h per sq ft x an insulation factor and a sun factor, plus 600 BTU/h for one person and 1,500 W of tools at 3.412 BTU/h per watt (about 5,118 BTU/h). All of those factors are conventions, not code values, and a contractor load calculation is the right answer for a big purchase. Remember the open overhead door: a mini-split cannot beat an open 16 ft door.

Check each unit's voltage before you plan the circuit. Some DIY 12,000 BTU units run on 115V; others need a 208-240V circuit and a disconnect, which changes the subpanel size. Have a licensed electrician confirm.

Shop for this size

Matched to the result above.

Prices change often; the button shows today's price on Amazon.

Get the garage shop planning checklist

One printable page: measure the bay, count the circuits, list the machines, check the floor. Plus a few short emails, then a couple a month at most.

Unsubscribe anytime. You can also just read the checklist on this site.

Mini-split by garage size: the other answers

Frequently asked questions

Is a 12,000 BTU mini-split enough for a 20x20 two-car garage?

With average insulation, normal sun and one person with 1,500 W of tools, the load here is about 15,718 BTU per hour, so a 12,000 BTU unit is undersized. Look at the 18,000 BTU size.

This page is researched guidance, not professional electrical, engineering or safety advice. Circuits, loads and clearances depend on your house, your service and your town: have a licensed electrician confirm any wiring, and check local code and each manufacturer's manual before you act.